Chapter 7: Using the Web Interface
452
4.
Observe the Power Control status of the monitored device to make sure
the power-on operation succeeds.
Editing or Deleting Ping Monitoring Settings
You can edit the ping monitoring settings of any IT device or simply delete it if
no longer needed.
To modify or delete any monitored IT device:
1.
Choose Device Settings > Server Reachability.
2.
Click the desired one in the list.
3.
Perform the desired action.
To modify settings, make necessary changes and then click Save. For
information on each field, see
page 447).
To delete it, click
Example: Ping Monitoring and SNMP Notifications
In this illustration, it is assumed that a significant PDU (IP address:
192.168.84.95) shall be monitored by your PX3TS to make sure that PDU is
properly operating all the time, and the PX3TS must send out SNMP
notifications (trap or inform) if that PDU is declared unreachable due to power
or network failure. The prerequisite for this example is that the power sources
are different between your PX3TS and the monitored PDU.
This requires the following two steps.
Step 1: Set up the ping monitoring for the target PDU
1.
Choose Device Settings > Server Reachability.
2.
Click
3.
Ensure the "Enable ping monitoring for this server" checkbox is selected.
4.
Enter the data shown below.
Enter the server's data.
Field
IP address/hostname
To make the PX3TS declare the accessibility of the monitored PDU
every 15 seconds (3 pings * 5 seconds) when that PDU is accessible,
enter the following data.
Field
Number of successful pings to enable feature
Monitoring Server Accessibility
on the top-right corner.
.
Data entered
192.168.84.95
Data entered
3
(on