3.
Affix an asset tag to the IT device. Then connect this asset tag to the
composite asset strip by plugging the tag connector into the tag port on
the composite asset strip. For details, see
to PX3TS
(on page 65).
4.
(Optional) For a chain, it is highly recommended using the cable ties to
help hold the weight of all connecting cables.
5.
Repeat Step 3 to connect IT devices to the other composite asset strips in
the chain.
Daisy-Chain Limitations of Composite Asset Strips
There are some limitations when daisy chaining composite asset strips
"AMS-Mx-Z," where x is a number.
The maximum cable length between composite asset strips is 2 meters,
but the total cable length cannot exceed 10 meters.
The maximum number of composite asset strips that can be daisy chained
depends on the Raritan product you purchased.
It is NOT supported to hot swap or hot plug any AMS-Mx-Z in a composite
asset strip chain that has been connected to Raritan's PDU, SRC, or PMC.
Therefore, first disconnect the chain from the device when you need to
swap or add any AMS-Mx-Z to the chain.
Raritan devices
EMX2-111,
PX2 PDUs,
BCM1 (NOT BCM2 series)
Smart Rack Controller,
EMX2-888,
Chapter 4: Connecting External Equipment (Optional)
Connecting Regular Asset Strips
Maximum strips per chain
Up to 4 composite asset strips are