LEGRAND Raritan PX3TS User Manual page 590

Transfer switch
Table of Contents

Advertisement

Chapter 9: Using the Command Line Interface
570
Setting the Outlet Relay Behavior
This section applies to outlet-switching capable models only.
This command syntax determines the relay behavior of all outlets on a PX3TS
model.
config:#
pdu relayBehaviorOnPowerLoss <option>
Variables:
<option> is one of the options: latching or nonLatching.
Note: For more information on the outlet relay behavior, see
Relay Behavior
(on page 212).
Setting the Outlet Power-On Sequence
This section applies to outlet-switching capable models only.
This command sets the outlet power-on sequence when the PDU powers up.
config:#
pdu outletSequence <option>
Variables:
<option> is one of the options: default, or a comma-separated list of outlet
numbers.
Option
Description
default
All outlets are switched ON in the ASCENDING order
(from outlet 1 to the final outlet) when the PX3TS
powers up.
A comma-
All outlets are switched ON in the order you specify
separated list of
using the comma-separated list.
outlet numbers
The list must include all outlets on the PDU.
Note: Power-on sequencing is disabled in the latching mode. See
Latching Relay Behavior
(on page 212).
PX3TS Latching
PX3TS