Appendix C: Configuration or Firmware Upgrade with a USB Drive

Firmware Upgrade via USB

744
2.
The CLI generates and shows the encrypted form of "private."
3.
In the "config.txt" file, make the following changes to the SNMP write
community setting.
a.
Replace the word "private" with the encrypted value that CLI shows.
b. Add "encrypted:" to the beginning of that setting.
Firmware files are available on Raritan website's
(http://www.raritan.com/support/).
Note that if the firmware file used for firmware upgrade is the same as the
firmware version running on the PX3TS, no firmware upgrade will be
performed unless you have set the force_update option to true in the
"fwupdate.cfg" file. See
fwupdate.cfg
To use a USB drive to upgrade the PX3TS:
1.
Copy the configuration file "fwupdate.cfg" and an appropriate firmware
file to the root directory of the USB drive.
2.
Reference the firmware file in the firmware option of the "fwupdate.cfg"
file.
3.
Plug the USB drive into the USB-A port on the PX3TS.
4.
The PX3TS performs the firmware upgrade. The firmware upgrade
message "FUP" is displayed on the front panel display.
Tip: You can remove the USB drive and plug it into another PX3TS for
firmware upgrade when the firmware upgrade message displays.
5.
It may take one to five minutes to complete the firmware upgrade,
depending on your product.
6.
When the firmware upgrade finishes, the front panel display indicates the
firmware upgrade result.
Happy smiley: Successful.
Depending on your product, the happy smiley looks like one of the
following. For the first diagram, its background color will turn green.
Support page
(on page 734).