LEGRAND Raritan PX3TS User Manual page 592

Transfer switch
Table of Contents

Advertisement

Chapter 9: Using the Command Line Interface
572
Option
Description
lastKnownState
Restores all outlets to the previous status before
powering down the PX3TS when the PDU powers up
again.
Note: This feature does NOT take effect and cannot be configured on a PX3TS
device after the outlet relay is set to the "Latching" mode. See
Relay Behavior
(on page 212).
Setting the PDU-Defined Cycling Power-Off Period
This section applies to outlet-switching capable models only.
This command sets the power-off period of the power cycling operation for all
outlets.
config:#
pdu cyclingPowerOffPeriod <timing>
Variables:
<timing> is the time of the cycling power-off period in seconds, which is an
integer between 0 and 3600, or pduDefined for following the PDU-defined
timing.
Setting the Inrush Guard Delay Time
This section applies to outlet-switching capable models only.
This command sets the inrush guard delay.
config:#
pdu inrushGuardDelay <timing>
Variables:
<timing> is a delay time between 100 and 100000 milliseconds.
PX3TS Latching