Chapter 7: Using the Web Interface
266

Managed vs Unmanaged Sensors/Actuators

To manually manage or unmanage/release a sensor or actuator, see
Peripherals
(on page 258).
Managed sensors/actuators:
PX3TS communicates with managed sensors/actuators and retrieves their
data.
Managed sensors/actuators are always listed on the Peripheral Devices
page no matter they are physically connected or not.
They have an ID number as illustrated below.
They show one of the managed states. See
page 267).
For managed 'numeric' sensors, their readings are retrieved and displayed.
If any numeric sensor is disconnected or its reading cannot be retrieved, it
shows "unavailable" for its reading.
Unmanaged sensors/actuators:
PX3TS does NOT communicate with unmanaged sensors/actuators so their
data is not retrieved.
Unmanaged sensors/actuators are listed only when they are physically
connected to PX3TS.
They disappear when they are no longer connected.
They do not have an ID number.
They show the "unmanaged" state.
Sensor/Actuator States