Chapter 7: Using the Web Interface
200

Transfer Switch and Inlet Status

On the Transfer Switch page, a normal state's text color is black, a warning
state's is yellow, and a critical state's is red. See
Status of the transfer switch:
One or some of the following messages are displayed for indicating the transfer
switch state.
Message
Normal Operation,
Fully Redundant
Standby Inlet
Unavailable
Standby, Preferred
Inlet Unavailable
Standby, Retransfer
Pending
Standby, Retransfer
Possible
Transfer Switch
Status
"Normal" state.
▪ The preferred inlet is powering the outlets.
▪ The alternate inlet is in the normal or warning
state.
"Non-redundant" state.
▪ The preferred inlet is powering the outlets.
▪ The alternate inlet goes critical or is not
connected to power.
"Standby" state.
▪ The alternate inlet is powering the outlets.
▪ The preferred inlet goes critical or is not
connected to power.
"Standby" state.
▪ The alternate inlet is powering the outlets.
▪ The preferred inlet returns to normal, but
automatic retransfer is pending.
"Standby" state.
▪ The alternate inlet is powering the outlets.
▪ The preferred inlet returns to normal and you can
perform retransfer manually.
Tip: Automatic retransfer may be prevented because
of the automatic retransfer settings, but manual
retransfer is permitted. See
(on page 203).
(on page 193).
Power Transfer Settings