3.6

Commissioning of the "Actuating drive speed" technology application

Note!
Take all the necessary safety precautions before you carry out the following
commissioning steps and switch the device on!
Safety instructions with regard to commissioning
System constellation
8400 HighLine
U V W
M
3~
i
X3/AR
Reference voltage (10 V) for analog signals
X3/A1U
Speed setpoint selection (slider of setpoint potentiometer R)
• Scaling: 10 V ≡ 100 % ≡ 1500 rpm
X3/GA
Ground potential (GND) for analog signals
X5/RFR
Controller enable
X6
Diagnostic interface for connecting the USB diagnostic adapter
[3-1]
Block diagram for wiring the commissioning example for the "Actuating drive speed" application
Commissioning steps
Find a description of the commissioning steps of the "Actuating drive speed" technology
application below.
Please observe the sequence of the steps in the following chapters and follow them
through carefully. This will help you to commission your controller quickly and as safely as
possible:
Prepare controller for commissioning
Creating an »Engineer« project and going online
Parameterising the motor control
Parameterising the application
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Commissioning of the "Actuating drive speed" technology application
X3
AR A1U GA
24I RFR DI1 DI2
R
W
W
1k ... 10k
( 62)
( 63)
L
8400 HighLine C | Reference manual
( 54)
X5
DI3 DI4 DI5 DI6 DI7
1
(for a 4-pole motor)
( 60)
( 61)
Commissioning
DIAG
X6
X61
X6
59