8400 HighLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
FC03: Field controller limitation [xx.0123.00099]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The output of the field controller has reached its
maximum limit value. The drive is at the torque limit in
the field weakening range.
oC6: I2xt overload - motor [xx.0123.00105]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Thermal overload of the motor.
LP1: Motor phase failure [xx.0123.00145]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Motor phase failure - power section
• This error message is displayed if a motor phase
carries less current of one half-wave than set in
C00599.
Sd10: Speed limit - feedback system 12 [xx.0123.00200]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Maximally permissible speed of the feedback system
connected to DI1/DI2 reached.
Sd11: Speed limit for feedback system 67 [xx.0123.00201]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Maximally permissible speed of the feedback system
connected to DI6/DI7 reached.
596
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
L
Setting:
C00570/4
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Observe load requirements.
• Correct dimensioning or reduce setpoint from the
field weakening range if necessary.
Motor control
Setting:
C00606
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Observe load requirements.
• Correct dimensioning if necessary.
• In case of VFCplus operation: Check Vmin boost
(C00016).
Set
Vmin boost
Setting:
C00597
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Check the trigger threshold C00599.
Setting:
C00607
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
Reduce speed of the rotation shaft/feedback system.
n
<= (f
x 60) / encoder increment
encoder
max
(for f
= 10 kHz)
max
Setting:
C00607
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
Reduce speed of the rotation shaft/feedback system.
n
<= (f
x 60) / encoder increment
encoder
max
(for f
= 10 kHz)
max
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011