Lenze L-force HighLine C 8400 Series Reference Manual page 83

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

Functional principle of a switch-off positioning without pre-switch off
In case of the switch-off positioning without pre-switch off shown above, it makes sense
to use the
"Terminals
1. Set DI3 to HIGH level to activate CW rotation.
2. The drive accelerates along the acceleration ramp (C00012) up to the traversing speed
set in C00039/2.
3. After reaching the DI1 contact, the drive comes to a stop with quick stop (QSP) in the
target position.
4. Reset DI3 to LOW level and set DI4 to HIGH level to activate CCW rotation now.
5. The drive is accelerated along the acceleration ramp (C00012) up to the traversing
speed set in C00039/2.
6. After reaching the DI2 contact, the drive comes to a stop in the initial position with
quick stop (QSP).
Tip!
• In order to avoid positioning inaccuracy due to signal propagation delays, the
initiators can be directly evaluated by the drive controller. Limit switch
evaluation can be configured in the drive controller. In code
change the method of detecting position signals from level evaluation to edge
evaluation.
• In order to prevent unintended movements of the load in the target position,
the use of a holding brake is recommended as an alternative to DC-injection
braking (limited torque).
• The device terminals and their function assignment do not appear in the FB
Editor. The assignment of (hardware) terminals to (software) functions is
explained in the chapter
Commissioning steps
As shown in illustration [3-3], below find a description of the commissioning steps of the
"Switch-off positioning" application without pre-switch off.
Please observe the sequence of the steps in the following chapters and follow them
through carefully. This will help you to commission your controller quickly and as safely as
possible:
Prepare controller for commissioning
Creating an »Engineer« project and going online
Parameterising the motor control
Parameterising the application
Saving parameter settings safe against mains failure
Enable controller and test application
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Commissioning of the "Switch-off positioning" technology application
2" control mode:
"Terminal assignment of the control
( 84)
( 86)
( 87)
( 89)
L
8400 HighLine C | Reference manual
( 85)
( 89)
Commissioning
C00488/x
you can
modes".
( 428)
83