8400 HighLine C | Reference manual
Parameter reference
Structure of the parameter descriptions
Scaling factor
The "scaling factor" is important for parameter access via a bus system.
Signal type
Analog (scaled)
Angular velocity
Position in [units]
Digital (BOOL)
Time
Selection value
Example 1: The value "654" of the parameter
system must be divided by the corresponding scaling factor "100" to obtain the actual
display value "6.54 V".
[14-1] Conversion formula for read access via bus system
Example 2: In order to set the parameter
value "123.45 %" via a bus system, the integer value "12345" must be transferred, i.e. the
value to be set must be multiplied by the corresponding scaling factor "100".
[14-2] Conversion formula for write access via bus system
Character length
In case of parameters of "VISIBLE_STRING" data type, the character length is given in
addition. This is also important for the parameter access via a bus system.
708
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Scaling factor
100
1
10000
1
1000
1
Read value (via bus system)
---------------------------------------------------------------------- -
Scaling factor
Value to be written (via bus system)
L
Resolution
Value range
16 bits signed
± 199.99 %
16 bits signed
± 32767 incr./ms
32 bits signed
± 214748.3647 [units]
8 bits unsigned
0 ≡ FALSE; 1 ≡ TRUE
16 bits unsigned
0 ... 999.000 s
16 bits unsigned
0 ... 65535
C00028/1
(AIN1: input voltage) read via a bus
Indicated value (Engineer)
=
C00012
(acceleration time main setpoint) to the
Value to be set Scaling factor
=
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011