Blocking time
In
C00324/x
with the transmission type"asynchronous - manufacturer-specific/device profile-specific".
Example: Cycle time = 500 ms, blocking time = 100 ms, data change sporadically:
 In the case of a sporadic data change < 500 ms, due to the blocking time set, a
transmission takes place every 100 ms as quickly as possible (event-controlled
transmission). The transmission cycle timer is reset to 0 if "event-controlled
transmission" has been activated.
 In the case of a sporadic data change > 500 ms, due to the cycle time set, transmission
takes place every 500 ms (cyclic transmission).
Tip!
The communication parameters can also be set via the following CANopen objects:
I-1400
I-1800
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
a "blocking time" can be set which defines the shortest transmission cycle
... I-1402: Communication parameters for RPDO1 ... RPDO3
... I-1802: Communication parameters for TPDO1 ... TPDO3
L
8400 HighLine C | Reference manual
System bus "CAN on board"
Process data transfer
639