Lenze L-force HighLine C 8400 Series Reference Manual page 306

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

8400 HighLine C | Reference manual
Motor control (MCTRL)
Internal interfaces | system block "LS_MotorInterface"
Identifier
DIS code | data type
bIdentificationActive
bFlyingSyncActive
bHlgLoad
nHlgSetValue_a
bHlgStop
306
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Value/meaning
"Motor parameter identification active" status signal
Automatic motor data identification ( 137)
BOOL
TRUE Motor parameter identification is active
"Flying restart function active" status signal
Flying restart function ( 250)
BOOL
TRUE Flying restart function is active
Control signal for an additional loading function of the ramp function generator
•  L_NSet_1.bExternalCINH
BOOL
• To enable the ramp function generator to follow automatically when the
controller is inhibited, for jerk-free setpoint connection.
TRUE Set the ramp function generator to a setpoint of nHlgSetValue_a
Setpoint for an additional loading function of the ramp function generator
•  L_NSet_1.nCInhVal_a
INT
• For speed-controlled drive tasks, the current actual speed value (e.g. in case of an
active pulse inhibit, flying restart function, controller inhibit) is provided at this
output.
• Scaling: 16384 ≡ 100 % reference speed (C00011)
Control signal for stopping the ramp function generator (L_NSet_1)
BOOL
TRUE Stop the ramp function generator
L
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011