8400 HighLine C | Reference manual
Motor control (MCTRL)
Parameterisable additional functions
5.10.2

Operation with increased rated power

Under the operating conditions described here and under continuous operation, the
controller can be operated with a higher power motor (increased rated power). The
remaining overload capacity of the drive system (for 60 s/3 s) is reduced accordingly to
approx. 120 %/160 %.
Typical applications stand out due to low dynamic requirements, e.g. pumps and fans,
general horizontal materials handling technology and line drives.
The controllers that can be operated at increased rated power are listed in the
rated data in the 8400 hardware manual.
• The hardware manual has been stored in electronic form on the data carrier
supplied with the 8400 drive controller.
Stop!
Operation at increased rated power is only permitted ...
• with the controllers listed in the 8400 hardware manual for this type of
operation in the stated mains voltage range.
• at switching frequencies of 2 kHz and 4 kHz.
• at a max. ambient temperature of 40 °C.
• with the types of installation stated in the 8400 hardware manual.
• with the fuses, cable cross-sections, mains chokes, and filters as required in
the 8400 hardware manual for this operation.
• after parameterisation according to the specifications below.
Required parameterisation
Operation at increased rated power requires the following settings to be made particularly
for the V/f characteristic control (VFCplus), but also for all other types of control:
Parameter
C00016
C00018
C00021
C00120
C00123
C00173
246
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Info
VFC: Vmin boost
Switching frequency
Slip compensation
Setting of motor overload (I²xt)
Device utilisat. threshold (Ixt)
Mains voltage
L
Required setting
adapt to motor
(reduce)
1: 4 kHz var./drive-opt.
adapt to motor
adapt to motor
120 %
see hardware manual
 Rated data
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011