Lenze L-force HighLine C 8400 Series Reference Manual page 726

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

8400 HighLine C | Reference manual
Parameter reference
Parameter list | C00064
C00064
Parameter | Name:
C00064 | Device utilisation (Ixt)
Display of the device utilisation Ixt in different time resolutions
• If the value displayed here exceeds the threshold set in C00123, the fault message "OC5: Device overload (Ixt)"
is output and the fault response set in
Display range
(min. value | unit | max. value)
0.00
Subcodes
C00064/1
C00064/2
C00064/3
Read access
C00065
Parameter | Name:
C00065 | Supply voltage 24V
Display of the 24V supply voltage for the supply of the control electronics
Note:
The 24 V supply for the control electronics is either provided by an external supply or by the controller itself if it is
connected to the mains voltage.
Display range
(min. value | unit | max. value)
0.0
Read access
C00066
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Display of the thermal motor load, sensorlessly determined using a motor model
• If the value displayed here exceeds the motor overload setting (C00120), the fault message "OC6: Thermal motor
overload (I2xt)" is output and the fault response set in
Display range
(min. value | unit | max. value)
0.00
Read access
C00070
Parameter | Name:
C00070 | Vp speed controller
Amplification factor Vp of the speed controller for different motor control modes
Setting range
(min. value | unit | max. value)
0.00
Subcodes
C00070/1
C00070/2
C00070/3
Read access
726
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
C00604
%
Write access
CINH
PLC STOP
V
Write access
CINH
PLC STOP
%
Write access
CINH
PLC STOP
Lenze setting
15.00
6.00
3.00
Write access
CINH
PLC STOP
L
is executed (default setting: "Warning").
250.00
Info
Device utilisation (Ixt)
• Maximum value of the pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
Device utilisation (Ixt) 15s
• Pulse utilisation over the last 15 seconds (only for
loads >160 %).
Device utilisation (Ixt) 3 min
• Permanent utilisation over the last 3 minutes.
No transfer
COM
MOT
Scaling factor: 100
3276.7
No transfer
COM
MOT
Scaling factor: 10
C00606
is executed (default setting: "Warning").
199.99
No transfer
COM
MOT
Scaling factor: 100
600.00
Info
SLVC: Vp speed controller
SC: Vp speed controller
SLPSM: Vp speed controller
No transfer
COM
MOT
Scaling factor: 100
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Data type: INTEGER_16
Index: 24511
= 5FBF
d
h
Data type: INTEGER_16
Index: 24510
= 5FBE
d
h
Data type: INTEGER_16
Index: 24509
= 5FBD
d
h
Data type: UNSIGNED_16
Index: 24505
= 5FB9
d
h

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L-force highline e84avhc series

Table of Contents