Lenze L-force HighLine C 8400 Series Reference Manual page 752

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

8400 HighLine C | Reference manual
Parameter reference
Parameter list | C00174
C00174
Parameter | Name:
C00174 | Reduc. brake chopper threshold
The threshold from which on the brake chopper is controlled is reduced by the voltage value set here.
Setting range
(min. value | unit | max. value)
0
Read access
C00175
Parameter | Name:
C00175 | Brake energy management
From version 02.00.00
Selection of the braking procedure
Selection list
(Lenze setting printed in bold)
Read access
C00176
Parameter | Name:
C00176 | Undervoltage threshold for mains OFF
This code is for device-internal use only and must not be written to by the user!
C00177
Parameter | Name:
C00177 | Switching cycles
Counter of different switching cycles and stressful situations
Display range
(min. value | unit | max. value)
0
Subcodes
C00177/1
C00177/2
C00177/3
C00177/4
C00177/5
Read access
752
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
V
Write access
CINH
PLC STOP
0 R_Brems
1 RfgStop
2 R_Brems + HlgStop
3 FI_MotBrk + RfgStop
4 R_Brems + FU_MotBrk + HlgStop
Write access
CINH
PLC STOP
2147483647
Write access
CINH
PLC STOP
L
Lenze setting
150 0 V
No transfer
COM
MOT
Scaling factor: 1
Select response if the brake resistor is controlled
Info
The brake resistor is used. When the threshold voltage
(C00174) is exceeded, the brake resistor is energised.
The "Ramp function generator stop" signal
(MCTRL_bRfgStop) is used. When the threshold voltage is
exceeded (C00174), the ramp function generator is
stopped.
The brake resistor and the "Ramp function generator
stop" signal are used. When the threshold voltage is
exceeded (C00174), the brake resistor is energised and
the ramp function generator is stopped.
From version 04.00.00
Braking is performed by a superimposed speed setpoint
vibration in conjunction with "Ramp function generator
stop".
From version 04.00.00
Braking is performed by combining all three braking
procedures.
No transfer
COM
MOT
Scaling factor: 1
Info
Number of mains switching cycles
Number of switching cycles of the output relay
Short circuit counter
Earth fault counter
"Clamp" counter
No transfer
COM
MOT
Scaling factor: 1
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Data type: UNSIGNED_8
Index: 24401
= 5F51
d
h
Data type: UNSIGNED_8
Index: 24400
= 5F50
d
h
Data type: UNSIGNED_16
Index: 24399
= 5F4F
d
h
Data type: UNSIGNED_32
Index: 24398
= 5F4E
d
h