5.14.1
Device overload monitoring (Ixt)
C00064/1...3
Parameter
C00064/1
C00064/2
C00064/3
Highlighted in grey = display parameter
If the device utilisation reaches the switch-off threshold set in C00123:
– The error response set in
– The
"OC5: Ixt
– The bMctrlIxtOverload status output of the
set to TRUE.
A setting of
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
displays the device utilisation (ixt) in [%] in different time intervals:
Info
Device utilisation (Ixt)
• Maximum value of pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
Device utilisation (Ixt) 15s
• Pulse utilisation over the last 15 seconds (only for loads >160 %).
Device utilisation (Ixt) 3 min
• Permanent utilisation over the last 3 minutes.
C00604
overload" error message will be entered into the logbook.
C00604
= "0: No Reaction" deactivates the monitoring.
L
8400 HighLine C | Reference manual
will be carried out (Lenze setting: "Warning").
LS_DeviceMonitor
Motor control (MCTRL)
Monitoring
system block will be
289