8400 HighLine C | Reference manual
Device control (DCTRL)
Device commands (C00002/x)
4.1.1
Load Lenze setting
The
C00002/1
which are saved in the controller firmware.
Can only be executed if the controller is inhibited; otherwise, the feedback
= "6: No access - controller inhibit" will be returned.
All parameter changes which have been carried out after the last time the parameter
set was saved will be lost!
This device command has an effect on the settings of the parameters of the operating
system, application and module.
How to load the Lenze setting:
1. If the controller is enabled, it must be inhibited, e.g. by executing the
"Enable/Inhibit controller" device command
2. Execute the "Load Lenze setting" device command:
C00002/1
The loading process may take a couple of seconds. After the device command has
been called,
20%" "Work in progress 40 %" "Work in progress 60 %", etc.).
104
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
= "1: On / start" device command resets the parameters to the Lenze setting
= "1: On / start"
C00002/1
returns dynamic status information ("Work in progress
L
(C00002/16
= "0: Off / ready").
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
C00002/1