8400 HighLine C | Reference manual
Parameter reference
Parameter list | C00029
C00029
Parameter | Name:
C00029 | AINx: Input current
Display of the input current at the analog inputs
• When the corresponding analog input is configured for current measurement
• When
C00034/x
Display range
(min. value | unit | max. value)
0.00
Subcodes
C00029/1
C00029/2
Read access
C00033
Parameter | Name:
C00033 | AINx: Output value
Display of the output value in percent of the analog input amplifier
• 100 % ≡ 16384 ≡ +10 V / +20 mA
Display range
(min. value | unit | max. value)
-199.99
Subcodes
C00033/1
C00033/2
Read access
C00034
Parameter | Name:
C00034 | AINx: Configuration
Configuration of the analog inputs for current or voltage measurement
Selection list
Subcodes
C00034/1
C00034/2
Read access
C00036
Parameter | Name:
C00036 | DC braking: Current
Braking current in [%] based on rated device current (C00098)
Setting range
(min. value | unit | max. value)
0.00
Read access
722
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.
mA
Write access
CINH
PLC STOP
%
Write access
CINH
PLC STOP
0 -10V..+10V
1 0mA..20mA
2 4mA..20mA
Lenze setting
0: -10V..+10V
0: -10V..+10V
Write access
CINH
PLC STOP
%
Write access
CINH
PLC STOP
L
20.00
Info
AIN1: Input current
AIN2: Input current
No transfer
COM
MOT
Scaling factor: 100
199.99
Info
AIN1: Output value
AIN2: Output value
No transfer
COM
MOT
Scaling factor: 100
Info
Input signal is the voltage signal -10 V ... +10 V
• -10 V ... +10 V ≡ -100 % ... +100 %
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA ≡ 0 % ... +100 %
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA ≡ 0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
Info
AIN1: Config.
AIN2: Config.
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
200.00 50.00 %
No transfer
COM
MOT
Scaling factor: 100
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Data type: INTEGER_16
Index: 24546
= 5FE2
d
(C00034/x
= 1 or 2).
Analog terminals
Data type: INTEGER_16
Index: 24542
= 5FDE
d
Analog terminals
Data type: UNSIGNED_8
Index: 24541
= 5FDD
d
Analog terminals
Data type: INTEGER_16
Index: 24539
= 5FDB
d
DC-injection braking
h
h
h
h