3.2

Notes on motor control

In the Lenze setting, the V/f characteristic control (VFCplus) as motor control is set in
C00006
with a linear characteristic.
 V/f characteristic control (VFCplus) is a motor control mode for classic frequency
inverter applications on the basis of a simple and robust control procedure for the
operation of machines with a linear or quadratic load torque characteristic (e.g. fans).
 The presettings of the parameters ensure that the controller is ready for operation right
away and the motors works adequately without further parameterisation if a
controller and a 50 Hz asynchronous machine with matching performances are
assigned.
Note!
Check the nameplate data against the motor data set in the controller. Further
information is provided in the chapter
Recommendations for the following application cases:
 If the controller and motor differ greatly in terms of performance:
Set the Imax limit (in motor mode) in
 If a high starting torque is required:
When the motor is idling, set a value for Vmin boost in
rated motor current flows at a field frequency of f = 3 Hz (display in C00058).
 For noise optimisation:
In C00018, set a switching frequency of "16 kHz var./drive-opt.".
 If a high torque must be provided at small speeds without feedback:
Select "Sensorless vector control (SLVC) as motor control mode in C00006.
Related topics:
Motor control (MCTRL)
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
8400 HighLine C | Reference manual
"Motor selection/Motor
C00022
( 131)
L
Notes on motor control
data".
to 2x rated motor current.
C00016
which ensures that the
Commissioning
( 132)
55