8400 HighLine C | Reference manual
Parameter reference
Parameter list | C00905
C00905
Parameter | Name:
C00905 | Motor phase direction of rotation
From version 04.00.00
In case of a control mode selected in
controller can be reversed by selecting "1: Inverted" to correct such misconnected motor phases. In this case, a phase
will be reversed at the output of the inverter.
Note:
For control modes with actual speed feedback or
must always be set).
Selection list
(Lenze setting printed in bold)
Read access
C00909
Parameter | Name:
C00909 | Speed limitation
Max. positive/negative speed for all motor control modes
Setting range
(min. value | unit | max. value)
0.00
Subcodes
C00909/1
C00909/2
Read access
C00910
Parameter | Name:
C00910 | Frequency limitation
Max. positive/negative output frequency for all motor control modes
Setting range
(min. value | unit | max. value)
0
Subcodes
C00910/1
C00910/2
Read access
C00915
Parameter | Name:
C00915 | Motor cable length
Single motor cable length for calculating the motor cable resistance
• The calculated motor cable resistance is displayed in C00917.
Setting range
(min. value | unit | max. value)
0.0
Read access
C00916
Parameter | Name:
C00916 | Motor cable cross-section
Motor cable cross-section of a phase/cable for calculating the motor cable resistance
• The calculated motor cable resistance is displayed in C00917.
Setting range
(min. value | unit | max. value)
0.50
Read access
900
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
C00006
without actual speed feedback, the output rotating field of the
0 not inverted
1 inverted
Write access
CINH
PLC STOP
%
Lenze setting
120.00 %
120.00 %
Write access
CINH
PLC STOP
Hz
Lenze setting
1000 Hz
1000 Hz
Write access
CINH
PLC STOP
m
Write access
CINH
PLC STOP
mm^2
Write access
CINH
PLC STOP
L
SLPSM
control mode, this function cannot be used ("not inverted"
No transfer
COM
MOT
Scaling factor: 1
175.00
Info
Max. pos. speed
Max. neg. speed
No transfer
COM
MOT
Scaling factor: 100
1000
Info
Max. pos. output frequency
Max. neg. output frequency
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
1000.0 5.0 m
No transfer
COM
MOT
Scaling factor: 10
Lenze setting
100.00 6.00 mm^2
No transfer
COM
MOT
Scaling factor: 100
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Data type: UNSIGNED_8
Index: 23670
= 5C76
d
h
Data type: INTEGER_16
Index: 23666
= 5C72
d
h
Data type: UNSIGNED_16
Index: 23665
= 5C71
d
h
Data type: UNSIGNED_16
Index: 23660
= 5C6C
d
h
Data type: UNSIGNED_16
Index: 23659
= 5C6B
d
h