8400 HighLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
Su06: Mains input overload [xx.0111.00006]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Overtemperature in case of devices from type 6 in the
input rectifier or the mains choke.
oH4: Heatsink temp. > shutdown temp. -5°C [xx.0119.00000]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The heatsink temperature now only differs by 5 °C from
the shutdown temperature of the motor.
oH1: Overtemperature heatsink [xx.0119.00001]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The heatsink temperature is higher than the fixed limit
temperature (90 ° C).
Maybe the ambient temperature of the controller is too
high or the fan or its ventilation slots are dirty.
oH3: Motor temperature (X106) triggered [xx.0119.00015]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The motor temperature monitoring function at the plug
connector X106, terminal T1 /T2, has tripped.
Possible causes:
• The motor is overheated so that the thermal contact
integrated into the motor has been switched.
• An open circuit or a loose contact at the connections
mentioned above has occurred.
oC5: Ixt overload [xx.0119.00050]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The Ixt overload check has tripped.
• Operating threshold = 100 % Ixt (adjustable in
C00123)
Possible causes:
• Wrong dimensioning of the device with regard to its
motor load.
• Load cycles are not complied with.
590
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
L
4: WarningLocked
5: Warning
6: Information
Remedy
• Check whether all mains phases are connected (a 2-
phase supply may be existent).
• Provide for sufficient cooling of the device.
Setting:
C00582
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
Prevent further heating, i.e. reduce motor load or set
controller inhibit so that the heatsink can cool down
again.
4: WarningLocked
5: Warning
6: Information
Remedy
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
• If required, clean or replace the fan.
• Provide for sufficient cooling of the device.
Setting:
C00585
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.
Setting:
C00604
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Check and, if required, correct dimensioning of the
device and the motor load with regard to technical
data.
• Reduce motor load cycles (observe load cycles
according to documentation).