Lenze L-force HighLine C 8400 Series Reference Manual page 730

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

8400 HighLine C | Reference manual
Parameter reference
Parameter list | C00083
C00083
Parameter | Name:
C00083 | Motor rotor time constant
Display of the rotor time constant of the motor
• This value is calculated from the rotor resistance and the rotor inductance (leakage and magnetising
inductance).
Display range
(min. value | unit | max. value)
0
Read access
C00084
Parameter | Name:
C00084 | Motor stator resistance
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
0
Read access
C00085
Parameter | Name:
C00085 | Motor stator leakage inductance
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
0.00
Read access
C00087
Parameter | Name:
C00087 | Rated motor speed
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor speed for the sensorless vector control (SLVC) and the servo control (SC).
Setting range
(min. value | unit | max. value)
50
Read access
C00088
Parameter | Name:
C00088 | Rated motor current
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range
(min. value | unit | max. value)
0.20
Read access
730
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
ms
Write access
CINH
PLC STOP
mOhm
Write access
CINH
PLC STOP
mH
Write access
CINH
PLC STOP
rpm
Write access
CINH
PLC STOP
A
Write access
CINH
PLC STOP
L
32767
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
200000 330 mOhm
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
650.00 3.50 mH
No transfer
COM
MOT
Scaling factor: 100
Lenze setting
60000 1460 rpm
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
320.00 21.00 A
No transfer
COM
MOT
Scaling factor: 100
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Data type: UNSIGNED_16
Index: 24492
= 5FAC
d
h
Data type: UNSIGNED_32
Index: 24491
= 5FAB
d
h
Data type: UNSIGNED_16
Index: 24490
= 5FAA
d
h
Data type: UNSIGNED_16
Index: 24488
= 5FA8
d
h
Data type: UNSIGNED_16
Index: 24487
= 5FA7
d
h