8400 HighLine C | Reference manual
Motor control (MCTRL)
Sensorless control for synchronous motors (SLPSM)
If the mass inertia of the drive is unknown, the optimisation can be achieved as follows:
1. Specify speed setpoint.
– A small speed just above the switching threshold is recommended in the closed-loop
controlled operation.
2. Increase Vp (C00070/3) until the drive starts to oscillate (observe engine noise).
3. Reduce Vp (C00070/3) until the drive runs stable again.
4. Reduce Vp (C00070/3) to approx. half the value.
5. Afterwards check results of the optimisation in the entire speed range (one-time
passing through of the speed range).
Tip!
Values recommended by Lenze for the setting of the (proportional) gain:
• For drive systems without feedback: Vp = 2 ... 8
• For drive systems with a good disturbance behaviour: Vp > 6
Speed controller reset time Ti
Apart from setting the P component,
on the I component of the PI controller.
If the mass inertia of the drive is unknown, the optimisation can be achieved as follows:
1. Specify speed setpoint.
2. Reduce Ti (C00071/3) until the drive starts to oscillate (observe engine noise).
3. Increase Ti (C00071/3) until the drive runs stable again.
4. Increase Ti (C00071/3) to approx. twice the value.
Tip!
Value range recommended by Lenze for the setting of the reset time:
Ti = 20 ms ... 150 ms
212
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
C00071/3
provides the possibility to take influence
L
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L-force highline e84avhc series

Table of Contents