How to adapt the peak current limitation:
V/f characteristic control (VFCplus):
• Reduce the slip compensation with C00021.
V/f control (VFCplus + encoder):
• Reduce the slip limitation to twice the rated motor slip with C00971.
• Reduce the V
Sensorless vector control (SLVC):
• Reduce the slip compensation with C00021.
• Reduce the limitation of the torque in motor mode via nTorqueMotLimit_a
(C00728/1) and the limitation of the torque in generator mode via
nTorqueGenLimit_a (C00728/2).
Servo control (SC):
• Reduce the jerk limitation with C00274.
• Reduce the limitation of the torque in motor mode via nTorqueMotLimit_a
(C00728/1) and the limitation of the torque in generator mode via
nTorqueGenLimit_a (C00728/2).
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
8400 HighLine C | Reference manual
boost in C00016.
min
L
Motor control (MCTRL)
Defining current and speed limits
149