C00597
Parameter | Name:
C00597 | Resp. to motor phase failure
Response to motor phase failure
• If a phase current does not exceed the threshold set in
will be triggered.
Selection list
(Lenze setting printed in bold)
Read access
C00598
Parameter | Name:
C00598 | Resp. to open circuit AINx
Configuration of monitoring of the analog inputs
Selection list
Subcodes
C00598/1
C00598/2
Read access
C00599
Parameter | Name:
C00599 | Motor phase failure threshold
Threshold for motor phase failure monitoring
• 100 % ≡ rated inverter current (C00098)
• If a phase current does not exceed the threshold set here for more than one period, the response to motor phase
failure set in
Setting range
(min. value | unit | max. value)
0.00
Read access
C00600
Parameter | Name:
C00600 | Resp. to DC bus voltage
Configuration of monitoring of the motor control (group 3)
Selection list
Subcodes
C00600/1
Read access
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
0 No Reaction
1 Fault
5 Warning
Write access
CINH
PLC STOP
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
5 Warning
Lenze setting
3: TroubleQuickStop
3: TroubleQuickStop
Write access
CINH
PLC STOP
C00597
will be triggered.
%
Write access
CINH
PLC STOP
1 Fault
2 Trouble
Lenze setting
2: Trouble
Write access
CINH
PLC STOP
L
8400 HighLine C | Reference manual
C00599
for more than one period, the response set here
No transfer
COM
MOT
Scaling factor: 1
Info
Response to open circuit at AIN1 if configured as
4 ... 20 mA current loop
Response to open circuit at AIN2 when being configured
as 4 ... 20 mA-current loop
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
100.00 5.00 %
No transfer
COM
MOT
Scaling factor: 100
Info
Response to DC bus undervoltage
No transfer
COM
MOT
Scaling factor: 1
Parameter reference
Parameter list | C00597
Data type: UNSIGNED_8
Index: 23978
= 5DAA
d
h
Data type: UNSIGNED_8
Index: 23977
= 5DA9
d
h
Analog terminals
Data type: INTEGER_16
Index: 23976
= 5DA8
d
h
Data type: UNSIGNED_8
Index: 23975
= 5DA7
d
h
813