Note!
For activated PC manual control:
The online connection between the PC and the controller is monitored by the
controller.
• If the online connection is interrupted for longer than the set timeout (Lenze
setting: 2 s):
– Error response "Fault" is triggered, i.e. the motor becomes torqueless and is
– The
PC manual control provides the Motion Control Kernel and the motor interface
with all required control signals and setpoint signals.
• The existing application (function block interconnection) is now decoupled
from these interfaces but will be processed as before and remains
unchanged.
• It does not matter what type of motor control is set in C00006.
How to activate PC manual control:
1. If an online connection to the controller has not been established yet:
Go online.
2. Go to Workspace and change to the Application parameters tab.
3. Go to the Overview dialog level and click the "PC manual control" button.
• The following safety note is displayed first:
• Click the Cancel button to abort the action and close the dialog box.
• The Timeout monitoring input field serves to adapt the timeout for monitoring
the connection between the PC and the controller.
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
coasting unless it already is at standstill.
"Ck16: Time overflow manual
the logbook.
L
8400 HighLine C | Reference manual
control" error message is entered into
Commissioning
PC manual control