5.4.3.1
Adapting the V/f base frequency
The V/f base frequency (C00015) determines the slope of the V/f characteristic and has
considerable influence on the current, torque, and power performance of the motor.
The setting in
Mains fluctuations or fluctuations of the DC-bus voltage (operation in generator mode)
do not need to be considered when the V/f base frequency is set. They are
automatically compensated for by the internal mains voltage compensation of the
device.
Depending on the setting in C00015, it may be required to adapt the reference speed
(C00011) to traverse the entire speed range of the motor.
The V/f base frequency is automatically calculated from the stored motor nameplate
data by the motor parameter identification:
V
frequency inverter
U
: Rated motor voltage depending on the connection method
ratedmot
f
: Rated motor frequency
rated
[5-4]
Calculation of the V/f base frequency
Typical values of the V/f base frequency
Drive controller with 400 V mains connection
Motor voltage [V]
230 / 400
220 / 380
280 / 480
400 / 690
400
230 / 400
280 / 480
400
220 / 380
Drive controller with 230 V mains connection
Motor voltage [V]
230
220 / 380
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
C00015
applies to all permitted mains voltages.
C00015 [Hz]
: Mains voltage 400 V or 230 V
Motor frequency [Hz]
50
50
60
50
50
50
60
87
50
Motor frequency [Hz]
50
50
L
8400 HighLine C | Reference manual
V/f characteristic control (VFCplus)
U
[V]
FI
--------------------------------- - f
⋅
[Hz]
=
Rated
U
[V]
Ratedmot
Motor connection
Motor connection
Motor control (MCTRL)
V/f base frequency
(C00015)
50 Hz
52.6 Hz
50 Hz
50 Hz
87 Hz
90.9 Hz
V/f base frequency
(C00015)
50 Hz
52.3 Hz
157