8400 HighLine C | Reference manual
Motor control (MCTRL)
Parameterisable additional functions
4. Set the flying restart current in C00994.
We recommend setting a flying restart current of 10 % ... 25 % of the rated motor
current.
• During a flying restart process, a current is injected into the motor to identify
the speed.
• Reducing the current causes a reduction of the motor torque during the flying
restart process. A short-time starting action or reversing of the motor is
prevented with low flying restart currents.
• An increase of the current improves the robustness of the flying restart
function.
Tip!
Use of motors with higher rated frequencies
For trouble-free operation, we recommend to manually enter a starting frequency
of 20 % of the rated motor frequency in
restart process (see above) and to use a lower flying restart current (10 % of the
rated motor current) if motors with higher rated frequencies are used.
Optimisation of the flying restart time
From version
via the setting of the integration time (C00993). A reduction of the integration
time causes the flying restart function to accelerate and thus a reduced flying
restart time.
• We recommend not to change the Lenze setting of the integration time.
• When special motor are used (e.g. multi-pole motors or ASM servo motors), a
reduced integration time may improve the flying restart behaviour.
Optimising the current controller if the behaviour is unstable
During the execution of flying restart function, peak currents/torques are avoided
by controlling the current amplitude.
Gain (C00075) and reset time (C00076) of the current controller can be adapted to
improve the jerk-free/torque-free connection of the inverter to the supply of the
rotating motor.
• We recommend not to change the Lenze setting of the current controller.
• If the behaviour of the current controller is unstable, gain and reset time can be
calculated as per the following formulae:
V
p
T
i
[5-23] Formulae for the calculation of the gain and reset time of the current controller
252
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
05.00.00, the duration of the flying restart process can be influenced
V
= Current controller gain (C00075)
p
L
H
[ ]
ss
T
= Current controller reset time (C00076)
i
=
--------------- -
T
s [ ]
L
= Motor stator leakage inductance (C00085)
ss
E
R
= Motor stator resistance (C00084)
s
T
= Equivalent time constant (= 500 μs)
E
L
[ ]
H
ss
=
--------------- -
R
[ ]
Ω
s
L
C00992
as well as to accelerate the flying
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011