5.10.5
DC-injection braking
Danger!
The DC-injection braking or auto DC-injection braking function cannot be used
with sensorless control for synchronous motors (SLPSM) and servo control (SC)
mode.
Holding braking is not possible when this braking mode is used!
• Use the basic
brake with a low rate of wear.
DC-injection braking allows the drive to be quickly braked to a standstill without the need
to use an external brake resistor.
The braking current is set in C00036.
The maximum braking torque to be generated by the DC braking current is approx.
20 ... 30 % of the rated motor torque. It is lower than that for braking in generator mode
with an external brake resistor.
Automatic DC-injection braking (auto DCB) improves the starting performance of the
motor when operated without speed feedback.
Tip!
DC-injection braking has the advantage that it is possible to influence the braking
time by changing the motor current or the braking torque..
Short overview of the relevant parameters:
Parameter
C00019
C00036
C00106
C00107
C00701/4
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
"Holding brake
control" function for controlling the holding
( 541)
Info
Auto-DCB: Threshold
• Operating threshold for activating DC-injection
braking
DC braking: Current
• Braking current in [%] based on rated device
current (C00098)
Auto-DCB: Hold time
DC braking: Hold time
LA_NCtrl: bSetDCBrake
• Selection of the signal source for activating DC-
injection braking
L
8400 HighLine C | Reference manual
Motor control (MCTRL)
Parameterisable additional functions
Dependent on the selected
Lenze setting
Value Unit
3 rpm
50 %
0.500 s
999.000 s
control mode
253