Lenze L-force HighLine C 8400 Series Reference Manual page 807

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

C00574
Parameter | Name:
C00574 | Resp. to brake resist. overtemp.
Response which is triggered if the threshold set in
Selection list
(Lenze setting printed in bold)
Read access
C00576
Parameter | Name:
C00576 | SC: Field feedforward control
Point of action of the direct-axis current setpoint precontrol for an early reduction of the field current. In this way,
the acceleration behaviour can be improved in the field weakening range.
• The entry [%] refers to the slip of the asynchronous motor.
Setting range
(min. value | unit | max. value)
0
Read access
C00577
Parameter | Name:
C00577 | SC: Vp field weakening controller
Proportional gain of the field weakening controller
• When "0" is set, the P component of the controller is deactivated.
• The recommended setting is in the range between 0 and 0.0020
Setting range
(min. value | unit | max. value)
0.0000
Read access
C00578
Parameter | Name:
C00578 | SC: Tn field weakening controller
Time constant of the field weakening controller
• The recommended setting is in the range between 10 and 30 ms
Setting range
(min. value | unit | max. value)
0.1
Read access
C00579
Parameter | Name:
C00579 | Resp. to max. speed/output freq. reached
Response when the max. speed limit (C00909) or output frequency limit (C00910) has been reached.
Selection list
(Lenze setting printed in bold)
Read access
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
0 No Reaction
1 Fault
5 Warning
Write access
CINH
PLC STOP
%
Write access
CINH
PLC STOP
Write access
CINH
PLC STOP
ms
Write access
CINH
PLC STOP
0 No Reaction
1 Fault
5 Warning
Write access
CINH
PLC STOP
L
8400 HighLine C | Reference manual
C00572
for monitoring brake resistor utilisation is reached.
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
600 200 %
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
2.0000 0.0010
No transfer
COM
MOT
Scaling factor: 10000
Lenze setting
6000.0 20.0 ms
No transfer
COM
MOT
Scaling factor: 10
No transfer
COM
MOT
Scaling factor: 1
Parameter reference
Parameter list | C00574
Data type: UNSIGNED_8
Index: 24001
= 5DC1
d
h
Data type: UNSIGNED_16
Index: 23999
= 5DBF
d
h
Data type: UNSIGNED_16
Index: 23998
= 5DBE
d
h
Data type: UNSIGNED_16
Index: 23997
= 5DBD
d
h
Data type: UNSIGNED_8
Index: 23996
= 5DBC
d
h
807