Auto-Start Option "Inhibit At Lenze Setting - Lenze L-force HighLine C 8400 Series Reference Manual

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

8400 HighLine C | Reference manual
Device control (DCTRL)
Automatic restart after mains connection/fault...
4.3.2

Auto-start option "Inhibit at Lenze setting"

This function extension is available from version 06.00.00!
The "Inhibit at Lenze setting" auto-start option configurable via bit 4 of
the change to the "SwitchedOn" status after the Lenze setting has been loaded and the
controller is enabled.
For a change to the "SwitchedOn" status, the controller enable must first be deactivated
after the Lenze setting has been loaded. Only if the controller is enabled again afterwards,
the status changes to "OperationEnabled":
Loading of the Lenze setting not possible since controller inhibit not set.
Controller inhibit via signal change by the user
Loading of the Lenze setting via device command
Controller enable via signal change by the user
Controller inhibit and subsequent controller enable via signal change by the user
t
= time required for loading the Lenze setting
load
[4-2]
Example 1: Behaviour with activated auto-start option "Inhibit at Lenze setting" (C00142: Bit 4 = "1")
Loading of the Lenze setting not possible since controller inhibit not set.
Controller inhibit via signal change by the user
Loading of the Lenze setting via device command
Controller enable via signal change by the user
t
= time required for loading the Lenze setting
load
[4-3]
Example 2: Behaviour with deactivated auto-start option "Inhibit at Lenze setting" (C00142: Bit 4 = "0")
124
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
C00002/1
= "1"
C00002/1
= "1"
L
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
C00142
prevents

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L-force highline e84avhc series

Table of Contents