C00018
Parameter | Name:
C00018 | Switching frequency
Selection of the pulse width modulated switching frequency transferred from the inverter to the motor
• Select between an ideal setting for the drive which provides smooth running, and an optimal setting with regard
to the inverter which keeps its losses to a minimum (min. Pv).
• Both possibilities offer fixed and variable switching frequencies.
• When a variable switching frequency is selected, the switching frequency may change as a function of the load
and rotational frequency.
Selection list
(Lenze setting printed in bold)
Read access
C00019
Parameter | Name:
C00019 | Auto DCB: Threshold
Setpoint speed threshold for automatic DC injection braking
• For speed setpoints with values below the thresholds a DC current is injected or the motor is not supplied with
current, depending on the setting.
Setting range
(min. value | unit | max. value)
0
Read access
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1 4 kHz var./drive-optimised
2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
5 2 kHz constant/drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised
11 4 kHz var./min. Pv
12 8 kHz var./min. Pv
13 16 kHz var./min. Pv
15 2 kHz constant/min. Pv
16 4 kHz constant/min. Pv
17 8 kHz constant/min. Pv
18 16 kHz constant/min. Pv
21 8 kHz var./drive-opt./4 kHz min
22 16 kHz var./drive-opt./4 kHz min
23 16 kHz var./drive-opt./8 kHz min
31 8 kHz var./min. Pv/4 kHz min
32 16 kHz var./min. Pv/4 kHz min
33 16 kHz var./min. Pv/8 kHz min
Write access
CINH
PLC STOP
rpm
Write access
CINH
PLC STOP
L
8400 HighLine C | Reference manual
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
60000 3 rpm
No transfer
COM
MOT
Scaling factor: 1
Parameter reference
Parameter list | C00018
Data type: UNSIGNED_8
Index: 24557
= 5FED
d
Selection of switching frequency
Data type: UNSIGNED_16
Index: 24556
= 5FEC
d
DC-injection braking