8400 HighLine C | Reference manual
Parameter reference
Parameter list | C00007
C00007
Parameter | Name:
C00007 | Control mode
With this parameter the control mode for the technology application selected under
inputs and outputs of the technology application are connected to the I/Os of the controller.
• How the inputs and outputs are connected in the individual control modes is described in the corresponding
technology application:
"Actuating drive speed" TA
TA "Table positioning"
"Switch-off positioning" TA
Selection list
(Lenze setting printed in bold)
Read access
Terminal assignment of the control modes 10 ... 16
Note: The following tables only list the connected inputs/outputs.
Input/output
RFR
DI1
DI2
DI3
DI4
A1U, A1I
O1U, O1I
DO1
Relay output
714
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
0 Wiring has changed
10 Terminals 0
12 Terminals 2
14 Terminals 11
16 Terminal 16
20 Keypad
21 PC
30 CAN
40 MCI
Write access
CINH
PLC STOP
10: Terminals 0
Fixed setpoint 1/3
Fixed setpoint 2/3
Activate manual DC-injection
braking (DCB)
Change of direction of rotation
Main speed setpoint (10 V ≡ 100 % reference speed)
Actual speed value (10 V ≡ 100 % reference speed)
Status "Drive is ready"
Status "Error is pending"
L
Info
This is displayed when the FB interconnection has been
changed in the I/O level via the FB Editor.
The technology application is controlled via the digital
and analog input terminals of the controller.
• For a short overview of the preconfigured terminal
assignment see the following section
assignment of the control modes 10 ...
The technology application is controlled via the keypad.
The technology application is controlled via the "Free
parameters" of the controller (PC control).
The technology application is controlled by means of
CAN-PDOs via the system bus "CAN on board".
System bus "CAN on board"
The technology application is controlled by means of
MCI-PDOs via the MCI-interface of an attached
communication module (e.g. PROFIBUS).
No transfer
COM
MOT
Scaling factor: 1
"Actuating drive speed" TA
12: Terminals 2
14: Terminals 11
Controller enable / Reset of error message
Change of direction of
rotation
Activate manual DC-
injection braking (DCB)
Quick stop
Motor potentiometer:
Increase speed
Motor potentiometer:
Decrease speed
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Data type: UNSIGNED_16
Index: 24568
= 5FF8
d
h
C00005
is defined, i.e. how the
"Terminal
16".
16: Terminals 16
Fixed setpoint 1/3
Fixed setpoint 2/3
CW rotation quick stop
CCW rotation quick stop