8400 HighLine C | Reference manual
I/O terminals
Digital input terminals
Counting behaviour
The following temporal characteristic shows the counting process depending on the
signals of the interfaces described before:
[6-1]
Transient characteristic of a quick counter block, sampling cycle = 1 ms
 The counter starts with the parameterised starting value.
 If the comparison value is reached or exceeded:
– The counter jumps back to its starting value.
– The output bCount1(6)_Compare is set to TRUE.
 If there is a FALSE-TRUE edge is at the input bCountIn1(6)_ResetCompare, the output
bCountIn1(6)_Compare can be reset to FALSE.
 If there is a FALSE-TRUE edge at the input bCountIn1(6)_LoadStartValue, the current
counter content can be reset to the parameterised starting value.
Related topics:
Using DI1(6) and DI2(7) as digital inputs
Using DI1(6) and DI2(7) as frequency inputs
Internal interfaces | System block "LS_DigitalInput"
322