8400 HighLine C | Reference manual
Device control (DCTRL)
Automatic restart after mains connection/fault...
Case 1: No controller enable at mains connection
If the controller is not enabled at mains connection, the controller remains in the
"SwitchedOn" status. Only with the controller enable, the device changes to the
"OperationEnabled" status, independent of the set auto-start option:
Case 2: Controller enable at mains connection and "Inhibit at power-on" activated
If the controller is enabled at mains connection and the auto-start option "Inhibit at power-
on" is activated, the controller remains in the "ReadyToSwitchOn" status. For changing to
the "SwitchedOn" status, the controller enable must first be deactivated. Only when the
controller is enabled again afterwards, the status changes to "OperationEnabled":
Case 3: Controller enable at mains connection and "Inhibit at power-on" deactivated
If in
C00142
the autostart option "Inhibit at power-on" is deactivated (bit 0 = 0), the status
first changes from "ReadyToSwitchOn" to "SwitchedOn" and then to "OperationEnabled"
after mains connection with an enabled controller:
L
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
123