Lenze L-force HighLine C 8400 Series Reference Manual page 595

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

FC01: Switching frequency reduction [xx.0123.00094]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Load-dependent switching frequency reduction
FC02: Maximum speed for Fchop [xx.0123.00095]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Maximum speed for chopper frequency has been
reached.
• The maximum speed has been exceeded depending
on the switching frequency.
oC14: Direct-axis current controller limitation [xx.0123.00096]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Direct-axis current controller limitation is active.
oC15: Cross current controller limitation [xx.0123.00097]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Cross current controller limitation is active.
oC16: Torque controller limitation [xx.0123.00098]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Actuator limitation according to speed controller.
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
L
8400 HighLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
Setting:
C00590
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control
Setting:
C00588
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
Select the correct maximum speed as a function of the
switching frequency.
Motor control: Defining speed limits
Setting:
C00570/1
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control
Setting:
C00570/2
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
• Check parameter setting of the current controller
with regard to the motor controllers (e.g. reduce Vp).
Motor control
Setting:
C00570/3
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control
595