8400 HighLine C | Reference manual
I/O terminals
Analog terminals
6.3.1.1
Signal adaptation by means of characteristic
This function extension is only available from version 04.00.00!
According to the illustration below, an individual characteristic can be parameterised for
the analog inputs via the subcodes of
a dead band. Here, the input signal corresponds to the X axis and the output signal
corresponds to the Y axis:
[6-4]
Characteristic for analog inputs
Parameter
C00010/1
C00010/2
C00010/3
C00010/4
C00010/5
C00010/6
C00010/7
C00010/8
C00020/1
C00020/2
C00020/3
C00020/4
C00020/5
C00020/6
C00020/7
C00020/8
In the »Engineer«, there is a parameterising dialog for entering the characteristic. This
dialog also displays the set characteristic graphically.
338
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
C00010
199.99 %
y
max
y
min
-x
max
-199.99 %
-199.99 %
Info
AIN1: (+y0) = min
AIN1: (+x0) = Dead band
AIN1: (-y0) = (-min)
AIN1: (-x0) = (-Dead band)
AIN1: (+ymax)
AIN1: (+xmax)
AIN1: (-ymax)
AIN1: (-xmax)
AIN2: (+y0) = min
AIN2: (+x0) = Dead band
AIN2: (-y0) = (-min)
AIN2: (-x0) = (-Dead band)
AIN2: (+ymax)
AIN2: (+xmax)
AIN2: (-ymax)
AIN2: (-xmax)
L
and
C00020
to provide different slopes and
199.99 %
x
max
-y
min
-y
max
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Lenze setting
Value Unit
0.00 %
1.00 %
0.00 %
1.00 %
199.99 %
199.99 %
199.99 %
199.99 %
0.00 %
1.00 %
0.00 %
1.00 %
199.99 %
199.99 %
199.99 %
199.99 %