C00324
Parameter | Name:
C00324 | CAN transmission blocking time
From version 06.00.00
Blocking time for the transmission of the emergency telegram and the process data
Note:
If the "Asynchronous - manufacturer-specific/device profile-specific" transmisson type is set, the transmission cycle
timer is reset to 0 if event-controlled transmission has been triggered.
Example: Cycle time (C00356/x) = 500 ms, blocking time = 100 ms, data change sporadically:
• In the case of a sporadic data change < 500 ms, due to the blocking time set, transmission takes place every
100 ms (event-controlled transmission) as quickly as possible.
• In the case of a sporadic data change > 500 ms, due to the cycle time set, transmission takes place every 500 ms
(cyclic transmission).
Setting range
(min. value | unit | max. value)
0
Subcodes
C00324/1
C00324/2
C00324/3
C00324/4
Read access
C00338
Parameter | Name:
C00338 | L_Arithmetik_1: Function
The
L_Arithmetik_1
Selection list
(Lenze setting printed in bold)
Read access
C00339
Parameter | Name:
C00339 | L_Arithmetik_2: Function
The
L_Arithmetik_2
Selection list
(Lenze setting printed in bold)
Read access
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
ms
Lenze setting
0 ms
0 ms
0 ms
0 ms
Write access
CINH
PLC STOP
FB: Selection of internal arithmetics
0 Out = In1
1 Out = In1 + In2
2 nOut_a = nIn1_a - nIn2_a
3 Out = (In1 * In2) / 100%
4 nOut_a = (nIn1_a * 1%) / |nIn2_a|
5 nOut_a = (nIn1_a * 100%) / (100% -
nIn2_a)
Write access
CINH
PLC STOP
FB: Selection of internal arithmetics
0 nOut_a = nIn1_a
1 nOut_a = nIn1_a + nIn2_a
2 nOut_a = nIn1_a - nIn2_a
3 nOut_a = (nIn1_a * nIn2_a) / 100%
4 nOut_a = (nIn1_a * 1%) / |nIn2_a|
5 nOut_a = (nIn1_a * 100%) / (100% -
nIn2_a)
Write access
CINH
PLC STOP
L
8400 HighLine C | Reference manual
6500
Info
CAN emergency blocking time
CAN1_OUT blocking time
CAN2_OUT blocking time
CAN3_OUT blocking time
No transfer
COM
MOT
Scaling factor: 1
No transfer
COM
MOT
Scaling factor: 1
No transfer
COM
MOT
Scaling factor: 1
Parameter reference
Parameter list | C00324
Data type: UNSIGNED_16
Index: 24251
= 5EBB
d
h
System bus "CAN on board"
Data type: UNSIGNED_8
Index: 24237
= 5EAD
d
h
Data type: UNSIGNED_8
Index: 24236
= 5EAC
d
h
767