The maximum number of the nodes to be monitored depends on the device version:
– "BaseLine C": 1 Heartbeat Producer can be monitored.
– "StateLine": Up to 7 Heartbeat Producers can be monitored.
– "HighLine": Up to 15 Heartbeat Producers can be monitored.
The node address(es) of the nodes to be monitored is/are set in
object I-1016, too.
Heartbeat event
The "Heartbeat event" is activated in the consumer if it does not receive any heartbeat
telegram from the producer within the heartbeat consumer time:
The consumer changes from the "Operational" communication status to the "Pre-
Operational" communication status.
The NMT master receives an emergency telegram containing emergency error code
0x8130.
The response parameterised in
Note!
The heartbeat monitoring will not start until the first heartbeat telegram of a
monitored producer has been received successfully and the "Pre-Operational"
NMT status has been assumed.
The boot-up telegram counts as the first heartbeat telegram.
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
8400 HighLine C | Reference manual
C00592/5
is activated (Lenze setting: "No response").
L
System bus "CAN on board"
Monitoring
C00385/1...n
or via
659