Lenze L-force HighLine C 8400 Series Reference Manual page 736

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

8400 HighLine C | Reference manual
Parameter reference
Parameter list | C00120
C00120
Parameter | Name:
C00120 | Setting of motor overload (I²xt)
Operating threshold for the "OC6: Motor overload (I²xt)" error message
• The response for reaching the threshold can be selected in C00606.
• The current thermal motor load is displayed in C00066.
Setting range
(min. value | unit | max. value)
0.00
Read access
C00123
Parameter | Name:
C00123 | Device utilisation threshold (Ixt)
Operating threshold for the "OC5: Device overload (Ixt)" error message
• The response for reaching the threshold can be selected in C00604.
• The current device utilisation is displayed in C00064.
Setting range
(min. value | unit | max. value)
0.00
Read access
C00129
Parameter | Name:
C00129 | Brake resistance value
From version 02.00.00
Resistance value of the connected brake resistor
• The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range
(min. value | unit | max. value)
0.0
Read access
C00130
Parameter | Name:
C00130 | Rated power - brake resistor
From version 02.00.00
Rated power of the connected brake resistor
• The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range
(min. value | unit | max. value)
0
Read access
C00131
Parameter | Name:
C00131 | Thermal capacity - brake resistor
Thermal capacity of the connected brake resistor
• The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range
(min. value | unit | max. value)
0.0
Read access
C00133
Parameter | Name:
C00133 | Brake resistor utilisation
Display of the utilisation of the connected brake resistor
Display range
(min. value | unit | max. value)
0
Read access
736
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
%
Write access
CINH
PLC STOP
%
Write access
CINH
PLC STOP
Ohm
Write access
CINH
PLC STOP
W
Write access
CINH
PLC STOP
kWs
Write access
CINH
PLC STOP
%
Write access
CINH
PLC STOP
L
Lenze setting
250.00 100.00 %
No transfer
COM
MOT
Scaling factor: 100
Lenze setting
200.00 100.00 %
No transfer
COM
MOT
Scaling factor: 100
Lenze setting
500.0 39.0 Ohm
No transfer
COM
MOT
Scaling factor: 10
Lenze setting
65535 100 W
No transfer
COM
MOT
Scaling factor: 1
Lenze setting
6553.5 10.0 kWs
No transfer
COM
MOT
Scaling factor: 10
65535
No transfer
COM
MOT
Scaling factor: 1
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Data type: INTEGER_16
Index: 24455
= 5F87
d
h
Data type: INTEGER_16
Index: 24452
= 5F84
d
h
Data type: UNSIGNED_16
Index: 24446
= 5F7E
d
h
Data type: UNSIGNED_16
Index: 24445
= 5F7D
d
h
Data type: UNSIGNED_16
Index: 24444
= 5F7C
d
h
Data type: UNSIGNED_16
Index: 24442
= 5F7A
d
h