8400 HighLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
oC1: Power section - short circuit [xx.0123.00016]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The device has recognised a short circuit of the motor
phases. To protect the device electronics, the inverter
control is switched off.
• Mostly, incorrectly executed motor connections are
the cause.
• If the device is inappropriately dimensioned with
regard to the motor load and the current limitation in
the controller (Imax controller) is set incorrectly, this
error message may also occur.
Motor control: Defining current limits
oC2: Power section - earth fault [xx.0123.00017]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The device has recognised an earth fault at one of the
motor phases. To protect the device electronics, the
inverter control is switched off.
• Mostly, incorrectly executed motor connections are
the cause.
• If motor filter, motor cable length, and cable type
(shielding capacity) are dimensioned incorrectly, this
error message may occur due to leakage currents to
PE.
• If motor filters with additional terminals for +UG and
–UG and devices greater or equal 3 kW are used, the
earth fault detection may be triggered due to leakage
currents to +UG and –UG.
• A cause can also be the use of shielded motor cables
longer than 50 m.
oC10: Maximum current reached [xx.0123.00030]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
The device displays that the maximum current has been
reached.
oC17: Clamp sets pulse inhibit [xx.0123.00031]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
Due to a short overcurrent, the inverter was switched off
for a short time (clamp disconnection).
592
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
L
4: WarningLocked
5: Warning
6: Information
Remedy
• Check motor connections and the corresponding plug
connector on the device.
• Only use permissible combinations of device power
and motor power.
• Do not set the dynamics of the current limitation
controller too high.
4: WarningLocked
5: Warning
6: Information
Remedy
• Check motor connections and the corresponding plug
connector on the device.
• Use motor filters, cable lengths, and cable types
recommended by Lenze.
• If motor filters with additional terminals for +UG and
–UG and devices greater or equal 3 kW are used:
Up to version V05.00.00:
(C00602) to "0: No Reaction".
From version V05.01.00:
detection during operation by setting a filter time
(C01770) of 250 ms.
• If motor cables longer than 50 m are used:
From version V05.01.00:
earth fault detection during operation (C01770).
4: WarningLocked
5: Warning
6: Information
Remedy
• Check and, if required, correct dimensioning of the
load with regard to the installed device power.
• Check the maximum current settings in
(Imax in motor mode) and
mode).
Setting:
C00569/1
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Check and, if required, correct dimensioning of the
load with regard to the installed device power.
• Reduce the dynamics of the setpoint change or speed
control.
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Set resp. to earth fault
Deactivate earth fault
Increase filter time for
C00022
C00023
(Imax in generator