8400 HighLine C | Reference manual
Basic drive functions (MCK)
Holding brake control
8.12.2.6
Motor magnetising time (only with asynchronous motor)
bMBrakeReleaseOut
I
BRK
Motor magnetising time
CINH = controller inhibit
[8-31] Considering the motor magnetising time taking the PM brake as an example
Related topics:
Process when brake is released
8.12.2.7
Actual value monitoring
If an actual value monitoring time > 0 s is selected in C02593/1, the actual speed time
monitoring is active.
The monitoring time starts when the speed setpoint has reached the lower switching
threshold and the actual speed is still above this threshold. (see illustration
chapter
If the actual speed is still above the threshold when the monitoring time has expired,
the brake will be automatically applied in the automatic brake control mode (mode 12).
Note!
In the Lenze setting, the actual speed time monitoring is deactivated
(C02593/1
reached the lower switching threshold.
552
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
CINH
( 553)
"Process when brake is
closed".)
= "0 s"), i.e. the brake will only be applied when the actual speed has
L
When an asynchronous motor is used,
first the magnetic field required for the
holding torque is created (which is
t
already available when a synchronous
motor is used) after the controller
inhibit is deactivated.
The motor is internally magnetised
t
through internal feedforward control
of the lower speed threshold. The
release time set in
t
considered here.
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
C02589/2
is
[8-34]
in