Lenze L-force HighLine C 8400 Series Reference Manual page 249

Inverter drives
Hide thumbs Also See for L-force HighLine C 8400 Series:
Table of Contents

Advertisement

Note!
The saturation characteristic is not only used for the correction of the current
controller but also influences the current controller feedforward control
(C00079/1).
Short overview of the relevant parameters:
Parameter
C02853/1...17
C02855
C02859
Distribution of the interpolation points
 The saturation characteristic is defined by 17 interpolation points which are distributed
linearly on the x axis.
 Interpolation point 17 represents 100 % of the maximum motor current in the process
(C02855).
1
Vp
[V/A]
Tn
[ms]
0
6.25
[5-22] Saturation characteristic: Distribution of the interpolation points
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Info
Lss saturation characteristic
Imax Lss saturation characteristic
Activate Lss saturation charact.
2
3
4
5
6
12.5
18.75
25
31.25
37.5
L
8400 HighLine C | Reference manual
Parameterisable additional functions
7
8
9
10
11
12
43.75
50
56.25
62.5
68.75
Motor control (MCTRL)
Lenze setting
Value Unit
100 %
3000.0 A
0: Off
13
14
15
16
17
I
max
75
81.25
87.5
93.75
100
[%]
249