8400 HighLine C | Reference manual
Motor control (MCTRL)
Braking operation/brake energy management
5.13.2.1

Inverter motor brake

This function extension is only available from version 04.00.00!
With this braking method, which can be selected as an alternative in C00175, the
regenerative
acceleration/deceleration with down-ramping of the ramp function generator..
Stop!
• This braking method only works without intervention of a position controller
in the case of speed-controlled applications!
• When the "inverter motor brake" function is used, the
(I2xt)
being thermally overloaded or the motor overload monitoring does not work
properly!
• The "inverter motor brake" function must not be used with vertical conveyors
(hoists) or with active loads!
Tip!
If no brake resistor is used, the DC injection brake can also be used for a braking
process in addition to the "inverter motor brake" and "Stopping of the ramp
function generator".
In applications with high mass inertia and long braking times (> 2 s), we
recommend the use of the DC injection brake.
• The DC injection brake provides for an oscillation-minimised braking. The
braking process generally takes more time than the "inverter motor brake"
function with an optimised setting. Moreover, the function is only
recommended for braking to a standstill.
In the following cases we recommend the "inverter motor brake" function:
• With servo control (SC).
• For all applications that do not require braking to a standstill (e.g.braking to a
lower speed setpoint) or the braking process can be interrupted by selecting a
new speed setpoint.
• For applications with low mass inertias and a short braking time (< 1 s).
• For all applications where braking should be as quick as possible.
284
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
energy
in
the
motor
is not adapted. If it is braked too frequently, there is a risk of the motor
DC-injection braking
L
is
converted
as
a
Motor load monitoring
( 253)
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011
result
of
dynamic

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L-force highline e84avhc series

Table of Contents