8400 HighLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
CE4: CAN bus off [xx.0131.00000]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
CAN on
board: "Bus off" status
• Received too many faulty telegrams.
• Damaged cable (e.g. loose contact).
• Two nodes have the same ID.
CA06: CAN CRC error [xx.0131.00006]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
CAN on
board: A faulty CAN telegram has been detected. • Check wiring and bus terminating resistor.
CA07: CAN bus warning [xx.0131.00007]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
CAN on
board: Incorrect transmission or reception of
more than 96 CAN telegrams.
• The current number of incorrectly transmitted CAN
telegrams is displayed in C00372/1.
• The current number of incorrectly received CAN
telegrams is displayed in C00372/2.
• The current CAN error status is displayed in C00345.
CA08: CAN bus stopped [xx.0131.00008]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
CAN on
board: The device has received the "Stop Remote
Node" NMT telegram.
CA0b: CAN HeartBeatEvent [xx.0131.00011]
Response (Lenze setting printed in bold)
0: No Reaction
Cause
CAN on
board: Cyclic node monitoring
• Being a Heartbeat consumer, the device has not
received a Heartbeat telegram from Heartbeat
producer 1 ... 15 within the defined time.
• The current statuses of the Heartbeat producers are
displayed in C00347/1...15.
598
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
1: Fault
2: Trouble
3: TroubleQuickStop
L
Setting:
C00592/2
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Setting:
C00592/1
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Eliminate electrical interference (e.g. EMC).
Setting:
C00592/3
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Setting:
C00592/4
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
Check CAN master (NMT master).
Setting:
C00592/5
(
Adjustable response)
4: WarningLocked
5: Warning
6: Information
Remedy
• Reactivate Heartbeat producers by mains switching,
restarting the controller, or a CAN Reset Node.
• Reparameterise CAN Heartbeat producer time or
switch off consumer monitoring and reset error
status if latched.
Heartbeat protocol
Firmware ≤ 11.00 - DMS 6.0 EN - 10/2011