Monitoring - Lenze C520 Commissioning

Hide thumbs Also See for C520:
Table of Contents

Advertisement

Assignment of the user data depending on the data type
Depending on the data type used, the user data is assigned as follows:
Data type
Length
String
x bytes
U8
1 byte
U16
2 bytes
U32
4 bytes
8.2.5

Monitoring

The parameters for setting network monitoring functions are described below.
Parameter
Address
Name / setting range / [default setting]
0x2859:001
PROFINET monitoring: Watchdog elapsed
0 No response
1 Fault > CiA402
2 Warning
0x2859:002
PROFINET monitoring: Data exchange exited
0 No response
1 Fault > CiA402
2 Warning
0x2859:003
PROFINET monitoring: Invalid configuration
0 No response
1 Fault > CiA402
2 Warning
0x2859:004
PROFINET monitoring: Initialisation error
0 No response
1 Fault > CiA402
2 Warning
0x2859:005
PROFINET monitoring: Invalid process data
0 No response
1 Fault > CiA402
2 Warning
Byte 1
Byte 2
Data
0x00
High byte
Low byte
Data
Data
High word
High byte
Low byte
Data
Data
Information
Selection of the response to a permanent interruption of the
communication to the IO controller.
Corresponding error code: 33168 | 0x8190 "PROFINET: Watchdog time-
out"
Selection of the response to exiting the "Data Exchange" state.
Corresponding error code: 33171 | 0x8191 "PROFINET: Exit Data
Exchange"
Selection of the response triggered by the reception of invalid
configuration data.
Corresponding error code: 33414 | 0x8286 "PROFINET: Configuration
error"
Selection of the response triggered by the occurrence of an error during
the initialisation of the network component.
Corresponding error code: 33170 | 0x8192 "PROFINET: Initialisation
error"
Selection of the response triggered by the reception of invalid process
data.
Process data marked as invalid (IOPS is "BAD") are received by the IO
Controller. Typically in case of
• a PLC in STOP state,
• alarms,
• acyclic demand data.
Corresponding error code: 33171 | 0x8193 "PROFINET: Invalid cyclic
process data"
Configuring the network
User data assignment
Byte 3
Byte 4
Data (x bytes)
Low word
High byte
Low byte
Data
Data
PROFINET
Monitoring
Byte ...
77