Download Print this page

Important Installation Information - LEGRAND Wattstopper LMDM-601-W Quick Start Manual

Dlm wireless dimming wall switch

Advertisement

WIRELESS ROOM CONNECTION
LMRC-611MCC
LMDM-601
Wireless
Dimmer
Sensor Params
LMPX-600
LMPC-600
Mode
Auto On
Blink
On
Load Type Dim
DLM Configuration App
on a mobile device
Distance Recommendations:
30' max between LMDM-601 and mobile device
60' max. between LMDM-601 and room controller or bridge
To ensure a successful installation and startup of a wireless system, the following steps must be taken by the
installing contractor. Failure to document all device address and locations may delay completion of startup
and result in additional startup charges.
Key Requirement: Document every Device's MAC Address (at least the last 4 alphanumeric characters). An
additional MAC address label is included for the installer to use on a floor plan map. The last four characters are
repeated in a larger font, in bold. Keep this document so that the commissioning tech has access at a later date.
Pair wireless devices to a room controller to create an individual room network and enable Plug N' Go operation.
Device pairing can be done by using Push-to-Pair (PtP) mode on the room controller and all other wireless devices, or by using the
DLM Config App.
To pair devices in a network, they must all have the same wireless channel and Network ID. By default the channel is 15 and the
Network ID is 1. Using Push-to-Pair mode, the Network ID for all devices being paired is migrated to a new number, so that only those
device communicate with each other. The channel number will remain at 15.
Push-to-Pair in a room with a single LMRC-611 Room Controller
NOTE: Once you enter PtP mode on the room controller, a three minute timer begins. If the Config button on any device in the room is
pressed, the timer resets and begins the three minute countdown again. If no Config button is pressed within three minutes, the
room controller will exit PtP mode.
1. Enter PtP mode on the room controller. Press the Config button three times (within three seconds) until the LED on the room
controller flashes green.
2. Enter PtP mode on the LMDM-601. Using a pointed tool, press the Config button three times. As with the room controller, the
LED on the switch will flash green.
3. Pair the LMDM-601. Press the Config button on the LMDM-601 one more time to pair it to the room controller. The load connected
to the room controller will toggle once (if the load is OFF, it will turn ON; if ON, it will turn OFF) to indicate that pairing was
successful. Also, the LMDM-601's blinking LED will turn to solid green as another indicator of a successful pairing.
NOTE: If there are any wireless sensors, dimmers, or additional switches in the room, repeat steps 2 and 3 for each of
those devices so that all devices are paired together in the same network. For each device, the load will toggle during
step 3 and its config LED will turn solid green.
4. Exit PtP mode. From any device, press the Config button 3 times. After a few seconds, the LED on each Room controller, switch
or sensor currently in PtP mode will flash white and reboot, leaving the default network and migrating to the new network. Then,
the LED on the room controller will flash blue and the pairing process finishes.The default Network ID on all devices will change to
a new number, based on the last four digits of the Mac address on the room controller, and now those devices will communicate
only with each other and not any devices which have not been paired.
NOTE: It is important to exit PtP mode within the three minute time limit mentioned above. If you do not, none of the device
pairings will be remembered and you have to start the process over from the beginning.
IPv6 Wireless communication
between DLM Room devices
over 6LoWPAN
IPv6 Mesh
Bluetooth low energy
communication for
mobile App support
Wireless
Sensor and/or
Photosensor

IMPORTANT INSTALLATION INFORMATION

SETTING UP A ROOM NETWORK BY PAIRING DEVICES
DEVICE PAIRING USING PUSH-TO-PAIR MODE
HYBRID ROOM CONNECTION
Room
LMDM-601
Controller
Wireless
(LMRC-112)
Dimmer
LMBC-650
Wireless
Network Bridge
Ceiling Mount
Sensor
Note: For a single (non-networked) hybrid room, the LMBR-650 is not required.
Note: The DLM Config App can only connect with the LMBC-650 to update firwmare or
pair devices. You need an LMBR-650 and LMCS to commision a Hybrid room. For a
single room, without an LMBR-650, LMCS can connect to the LMBC-650 via the LMCI.
2
Line
Load
Voltage
Examples
any relay)
(
Switched
Line Voltage
A
etc.
Switched with
B
B
0-10 Volt control
Class 1 Dimming
Dimming Ballast
(Class 2 also available)
LED Driver, etc.
LMBR-650
Sensor Params
Border Router
LMPX-600
LMPC-600
Mode
Auto On
Blink
On
Load Type Dim
DLM Configuration App
on a mobile device
Examples of labels

Advertisement

loading