Activating Additional Functions In The Signal Flow - Lenze E84AVSC Operating Instructions Manual

Controller/inverter drive
Table of Contents

Advertisement

8.2

Activating additional functions in the signal flow

The following parameters serve to activate further functions in the main signal flow that
are first deactivated by default:
Parameter
C00598/1
C00950/1
C00950/2
C00951
C00952
C00696
C00670
C00635
C00636
C0632/1...3
C0633/1...3
C00134
C00182
C02830
C00423
C00472/3
C00472/4
from Firmware V06.00 - DMS 1.1 EN - 11/2011
8400 StateLine C | Operating instructions
Name
Resp. to open circuit AIN1
Activation of signal interpolation
Activation of signal monitoring
L_Interpolator_1:
No. of interpolation steps
L_Interpolator_1:
Limit value - error cycles
L_OffsetGainP_1: Offset
L_OffsetGainP_1: Gain
L_NSet_1: nMaxLimit
L_NSet_1: nMinLimit
L_NSet_1: Blocking speed 1 ... 3 max
L_NSet_1: Blocking speed 1 ... 3 min
Ramp rounding - main setpoint
S-ramp time PT1
DIx: Debounce time
DOx: Delay times
LS_ParFree_a: Value 3
LS_ParFree_a: Value 4
L
Adapting the application individually
Activating additional functions in the signal flow
Info
Response to open circuit at the analog input when
being configured as 4 ... 20 mA current loop.
Lenze setting: "TroubleQuickStop". The drive is braked
to standstill within the deceleration time
parameterised for quick stop independently of the
defined setpoint and can be kept there.
Signal interpolation and monitoring
(see software manual; FB L_Interpolator_1)
Offset and gain
(see software manual; FB L_OffsetGainP_1)
Speed limit values ( 60)
Speed blocking zones ( 61)
Ramp smoothing ( 62)
Debounce and delay times for digital inputs and
outputs
Torque limitation in motor mode and in generator
mode. Lenze setting: 100 %
• The drive cannot output a higher torque in
motor/generator mode than set here.
• If V/f characteristic control (VFCplus) is selected,
limitation is indirectly performed via the Imax
controller.
59

Advertisement

Table of Contents
loading

This manual is also suitable for:

L-force 8400 series

Table of Contents