Maintenance-Object Repair Procedures
Table 8-207. Test #36 Port Audit and Update Test — Continued
Error
Test
Code
Result
Description / Recommendation
PASS
Trunk translation has been updated successfully. The current trunk states kept
in the DS1 Interface circuit pack and switch software are consistent. If the
trunk is busied out, the test will not run but will return PASS. To verify that the
trunk is in-service:
1. Enter status trunk to verify that the trunk is in-service. If the trunk is
2. Enter release trunk to put the trunk back into in-service.
3. Retry the test command.
0
NO
The test could not relate the internal ID to the port (no board). This could be
BOARD
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Verify that the board's translations are correct. Use the list config
2. If the board was found to be correctly inserted in step 1, issue the busyout
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command.
8-514
Issue 1 May 2002
in-service, no further action is necessary. If the trunk is out-of-service.
command, and resolve any problems that are found.
board command.
This should re-establish the linkage between the internal ID and the port. If
this is not the case, check to see that there is a valid board inserted.
Continued on next page